Switchgear & Protection Guide
Low-Voltage Switchgear

How to Size LV Switchgear Busbars for Load

Published 6 min read

copper busbar conductors mounted inside an electrical switchgear enclosure
Quick answer

To size LV busbars, calculate continuous load current, verify thermal ratings based on ambient temperature, and check voltage drop across joints and lengths. Select material and cross-section that meet IEC or local code limits.

Key takeaways
  • Size busbars for continuous load current plus a margin for thermal derating.
  • Use material-specific resistivity values for accurate voltage drop calculations.
  • Check mechanical clearances and insulation ratings for the selected conductor size.
  • Verify final selection against short-circuit withstand ratings and manufacturer data.

Prerequisites Before You Start

Sizing busbars is not just a current calculation. It is a system of thermal, electrical, and mechanical constraints. Before you pick a cross-section, gather the load schedule, the ambient temperature range, the installation layout, and the applicable standard.

The load schedule must list every downstream breaker, contactor, and feeder. For each point, note the rated current and the duty factor. A motor feeder running at 60 percent of full load is not the same thermal load as a resistive heater at 100 percent.

The ambient temperature matters because copper and aluminum expand and resist differently as heat builds up. A busbar in a hot server room or a tropical warehouse needs more cross-section than one in a climate-controlled basement.

Finally, confirm the material. Copper is the default for high-density panels and long runs. Aluminum is common in large-scale installations where weight and cost are driving factors. The two metals behave differently in every calculation step.

Step 1: Establish the Continuous Load Current

Start with the sum of all continuous loads supplied by the busbar. Continuous means the load is expected to run for three hours or more. Transient loads, like a single pump or a welding station, may be handled by a breaker, but they still add to the peak current.

Add the rated currents of all downstream feeders. Do not include demand factors unless the standard allows it. For a panel supplying a production line, every motor and heater is a continuous load.

Example: A busbar feeds three motor feeders at 50 A each and one resistor bank at 25 A. The continuous load is 175 A. If the busbar also serves a non-continuous lighting circuit at 10 A, the total design current is 185 A.

This number is your baseline. Every later step checks whether the conductor can survive it.

Step 2: Apply Ambient Temperature Derating

Copper and aluminum both lose carrying capacity as temperature rises. The standard derating curve reduces the rated current as ambient temperature increases above a reference value, usually 30 C or 40 C depending on the code.

For a busbar in a panel with limited ventilation, use the panel internal temperature, not the room temperature. A tightly packed cabinet with multiple breakers can run 10 to 20 C hotter than the surrounding air.

If the ambient is 40 C, a 250 mm square copper busbar rated for 400 A at 30 C may only carry 320 A. You must pick a larger cross-section to meet the design current.

For aluminum, the derating effect is more pronounced. A 400 mm square aluminum busbar may need to be upsized to a 450 mm square to match the thermal performance of a 250 mm square copper bar under the same ambient.

Step 3: Check the Voltage Drop

A busbar is not just a heat sink. It is a conductor with resistance. A long run with a high-resistance material will drop voltage before the current even reaches the load.

Use the formula: Voltage drop = current times resistance times length. Resistance depends on material resistivity, cross-section, and temperature. Copper has a lower resistivity than aluminum, so a copper busbar of the same size will drop less voltage.

For a 5 meter run at 185 A, a 250 mm square copper busbar drops very little voltage. But if you replace it with a 250 mm square aluminum bar, the drop increases significantly. If the load is sensitive, like a variable frequency drive or a precision instrument, the voltage drop must stay below 3 to 5 percent.

Always check the drop at the furthest point on the busbar. The far end sees the highest cumulative resistance.

Step 4: Verify Short-Circuit Withstand Rating

A busbar must survive a short circuit without melting or arcing. The short-circuit withstand rating depends on the material, cross-section, insulation, and mounting method.

For copper, a 125 mm square bar may withstand 10 kA for a standard time. For aluminum, the same bar may only withstand 8 kA. The difference is significant.

Check the maximum short-circuit current available at the busbar from the upstream transformer or switchgear. If the available fault current is 12 kA, you need a busbar rated for at least 12 kA. Do not guess. Use the manufacturer data sheet.

A common mistake is picking a busbar based on continuous current alone and forgetting the fault current. A busbar that carries 185 A easily can still fail if it is not rated for the fault current.

Step 5: Consider Mechanical Strength and Clearances

A busbar must stay in place during a short circuit. The electromagnetic force during a fault can be thousands of newtons. A thin, long busbar can vibrate, crack, or move out of alignment.

Check the mounting method. A busbar clamped to an insulator at both ends is different from one supported every 500 mm. The support spacing must match the manufacturer requirement.

Clearances are also mechanical. A larger busbar may not fit in a cramped panel. If you need to increase the cross-section, check the busbar channel width and the distance to the next phase.

For aluminum, the mechanical strength is lower than copper. A 400 mm square aluminum bar may need additional support compared to a 250 mm square copper bar of similar current rating.

Step 6: Select the Material and Cross-Section

Now you have the data. You know the continuous current, the ambient temperature, the voltage drop, the fault current, and the mechanical constraints. Pick the material first.

Copper is the default for panels with limited space, high fault currents, or long runs. It has a lower resistivity and a higher short-circuit withstand per square millimeter.

Aluminum is common for large plants, substations, or where weight is a concern. It is cheaper per square meter but needs more cross-section to carry the same current.

For the 185 A example at 40 C ambient with a 5 meter run and 12 kA fault current, a 250 mm square copper busbar may be sufficient. A 300 mm square aluminum bar may be required. The exact size depends on the standard and the manufacturer.

Use a table to compare. The table below shows typical ratings for common sizes at 30 C ambient. These are general values. Always confirm with the manufacturer data.

Material Cross-Section Rated Current Voltage Drop Trend Fault Current Trend
Copper 125 mm square 250 A Low High
Copper 250 mm square 400 A Low High
Copper 400 mm square 600 A Very Low Very High
Aluminum 250 mm square 320 A Moderate Moderate
Aluminum 400 mm square 500 A Moderate Moderate
Aluminum 600 mm square 700 A Low High

Pick the smallest cross-section that meets all criteria. Do not oversize. A 400 mm square copper busbar for a 185 A load wastes money and space.

Step 7: Final Verification and Documentation

Before you order, check the selection against the full set of constraints. Does it carry the continuous current at the actual ambient temperature? Does it drop less than 5 percent voltage at the far end? Does it withstand the fault current for the standard time? Does it fit the panel mechanically?

Document the calculation. Note the load, the ambient, the material, the cross-section, and the standard used. This document is part of the as-built record. If there is a fault or a modification later, the calculation is your reference.

A final check is to compare the selected busbar with similar installations. If a local engineer or a peer has used a similar size for a similar load, note it. If there is a discrepancy, investigate.

Common Mistakes

  • Ignoring ambient temperature. A busbar rated at 30 C is not the same at 50 C.
  • Using the wrong material resistivity. Copper and aluminum have different values. Do not mix them in the voltage drop formula.
  • Forgetting the fault current. A busbar that carries 185 A may not survive 12 kA.
  • Oversizing. A larger busbar costs more, takes more space, and may not fit the panel.
  • Not checking mechanical clearances. A 400 mm square busbar may not fit in a standard panel channel.

Final Verification Step

After you select the busbar, run the numbers one more time. Use the actual ambient temperature from the site survey, not the reference value. Use the actual material resistivity from the manufacturer data sheet. Check the voltage drop at the furthest point. Verify the short-circuit rating against the available fault current.

If any number fails, go back to step 2 or step 3. Do not just pick a larger cross-section without understanding why the original one failed.

A correctly sized busbar is safe, efficient, and economical. A poorly sized one is a future fault, a voltage drop complaint, or a panel that does not fit.

Frequently asked questions

What is the standard reference ambient temperature for busbar ratings?

Most standards use 30 C or 40 C as the reference. The manufacturer data sheet specifies the exact value. Always derate for higher ambient temperatures.

Can I use aluminum busbars in a panel with copper busbars elsewhere?

Yes, but you must use compatible terminations. Aluminum and copper react when exposed to moisture. Use anti-oxidant compound and proper torque on the connection.

How does busbar length affect voltage drop?

Longer busbars have higher resistance. The voltage drop increases with length. For long runs, consider increasing the cross-section or using a lower-resistance material.

Do I need to size busbars for future expansion?

Only if the standard requires it or if the load schedule includes a contingency. Otherwise, size for the current load. Adding a 50 percent margin is common practice but not always mandatory.

What is the typical short-circuit withstand time for LV busbars?

Most standards require 1 second or 0.1 second. The manufacturer data sheet specifies the exact time. Check the available fault current against the busbar rating.